Structured Cabling Systems

A Structured Cabling System (SCS) most simply stated is based on following a
standard methodology defined by EIA/TIA 568 specifications when planning and
installing network cabling for commercial buildings. The purpose of this
standard is to specify a generic telecommunications cabling system for
commercial buildings that will support a multi-product, multi-vendor
environment. It also provides information that may be used for the design of
telecommunications products for commercial enterprises.
By following these installation standards and using EIA/TIA compliant cabling
products when the network doesn’t work they can’t blame you! The whole point of
this standard that if followed the phone and networking equipment will work as
designed. No surprised, no performance issues. Life is good!
The EIA/TIA-568 standard includes EIA/TIA-568-B.1 General Requirements,
EIA/TIA-568-B.2 Copper Cabling Requirements, EIA/TIA-568-B.3 Fiber Cabling
Requirements. There are other requirements for very specific issues related to
these three but are not needed for this discussion. (Note to self – need to
cross reference Europe specs)
We will summarize each of the three standards separately, with the General
Requirements containing the most relevant information. (And I do mean summarize.
Between the three documents there are over 300 pages of extremely interesting
information (note the sarcasm)). We will also discuss variations of this
standard as it relates to the industrial environment.
EIA/TIA-568-B.1 General Requirements
We already talked about the purpose of this document. Requirements are defined
for the following areas of the Telecommunications Cabling System Structure (see
Figure 1)
- Horizontal cabling
- Backbone cabling
- Work Area
- Telecommunications Room
- Equipment Room
- Entrance Facilities
This structure is designed to support voice, data, text, video and image
services. A definition of terms is included at the end of this discussion.

Figure 1
Horizontal Cabling
The horizontal cabling is the portion of the telecommunications system that
extends from the work area to the telecommunications room. The horizontal
cabling includes horizontal cables, telecommunications outlet/connectors in the
work area, mechanical terminations, and patch cords or jumpers located in the
telecommunication room, and may include multi-user telecommunication outlet
assemblies and consolidation points.
Note the term “horizontal” is used since typically the cable in this part of
the cabling system runs horizontally in the building. Hmm. Makes sense!
The telecommunications room should be located on the same floor as the work
area served. Note the word “should”. This means it is preferred but not
required. When you see the word ‘shall” it means it must be done or the SCS cops
will teach you compliance!
(Actually there are no SCS cops. We will talk about how to test a SCS later).
Figure 2 illustrates a typical horizontal cabling run. Note bridge taps and
splices shall not (remember the word shall?) be installed as part of the copper
horizontal cabling. Splitters either. No more than one transition point or
consolidation point is allowed (We will talk about these later).

Figure 2
The maximum distance a horizontal run can be is 90 meters (295 feet). The
longest a patch cord can be is 5 meters (16 feet). And the longest total length
of patch cords on both ends can be 10 meters (32 feet).
The cables recognized by EIA/TIA include:
- Four-pair 100ohm unshielded twisted pair (UTP) or screened twisted pair
(ScTP) cables as defined in EIA/TIA-568-B.2
- Two or more optical fiber multimode cable, either 62.5um or 50/125 um
per EIA/TIA 568-B.3.
The standard also recommends that there “shall” be at least 2 connectors for
each work area; one Category 3 or higher (we will get to categories soon) and
the other number 1 or 2 above to support LAN services.
Backbone Cabling
The function of the backbone cabling is to provide interconnection between
telecommunication rooms, equipment rooms, main terminal space and entrance
facilities (did I forget the kitchen sink? Hey everything is being networked
today.) It includes the backbone cables, intermediate and main cross-connects,
mechanical terminations, and the patch cords or jumpers used for backbone to
backbone cross-connection. It also includes cabling between buildings.
The backbone cabling shall use the hierarchical star topology as illustrated
in Figure 3. From the horizontal cross-connect there shall be no more the one
additional cross-connect to reach the main cross-connect.

Figure 3
The cables used depend on the application Figure 4 list the maximum distance
requirements for the various cable runs. Note that the distances listed for
twisted pair cable is for supporting telephone use. To support higher network
speeds the 90 meter UTP length still applies back to the main cross-connect.

Figure 4
In the main cross-connect, jumper or patch cord lengths should not (note
“should” not “shall” so no beatings if you violate this one, though you could
get blamed if something doesn’t work!) exceed 20 m (66 ft). Same for the
intermediate cross-connect.
The length of the cable used to connect telecommunications equipment directly
to the main or intermediate cross-connect should not exceed 30 m (98 ft).
Work Area
The work area includes the telecommunications outlet/connector end of the
horizontal cabling system to the work station equipment (i.e. PC, PLC, etc.).
The work area outlet is either in the form of a faceplate or a box. Its
primary purpose is to hold the connector or modular jack. Per the standard each
4-pair cable shall be terminated in an eight-position modular jack per
EIA/TIA-568-B.2 and IEC 60603-7.
There are two cabling schemes approved, T568A and T568B (see figure 5). The
US Government only recognizes T568A, in case you wanted to know. The most common
however is T568B as it was the standard scheme used by AT&T during their golden
years as a monopoly.

Figure 5
For fiber cabling these shall be terminated to a duplex optical fiber
connector meeting the requirements of EIA/TIA-568-B.3. The SC connector is
preferred by EIA/TIA but others can be used such as the ST and various small
form factor connectors.
As already stated the maximum length allowed for the patch cord in the work
area is 5 m (16 ft). (Just stating it again in case you weren’t paying attention
the first time.)
MUTOA (Multi-user telecommunications outlet assembly)
Remember that I just told you the maximum length allowed for the patch cord in
the work area is 5 meters (hey you were paying attention)? Well there is an
exception and it is when you use a MUTOA (I am not typing this out twice).
This was added to the standard to address the growing use of modular
furniture in the commercial office. It provides a more flexible wiring means
that facilitates changes easier. See figure 6. It also complicates things a bit,
but as long as you follow the guidelines of Figure 7 you will stay compliant
(and avoid the SCS cops, blame, etc.) It is limited to serving a maximum of 12
work areas. It shall also be located in a fully accessible permanent location,
and not in ceilings.
Figure 6

Figure 7
Consolidation Point
One other twist in horizontal cabling includes the Consolidation Point. It is an
interconnection point within the horizontal cabling using the appropriate
compliant connecting hardware, including the requirements of being rated for at
least 200 cycles of connections. It also cannot be located within 15 m (49 ft)
of telecommunications room as it can cause cabling performance degradation due
to reflections.
The Consolidation Point may be useful when reconfiguration is frequent, but
not so frequent as to require the flexibility of the MUTOA.
The Telecommunications Room
The primary function of a telecommunications room is the termination of
horizontal and backbone cable to compatible connecting hardware. All connections
between horizontal and backbone cables shall be cross-connections. Equipment
cables/cords that extend a single port appearance may connected through an
interconnect.
So what is the difference between a cross-connect and an interconnect? Glad
you asked! Figure 8 shows the difference. When terminating a small amount of
cables (less than 100) an interconnect is fine. As the amount of connections
grow the cross-connect provides better overall cable management.

Figure 8
Equipment rooms are similar to Telecommunication Rooms except they typical
house more variety or complex equipment.
Entrance Facility
The Entrance Facility consist of cables, connecting hardware, protection
devices, and other equipment needed to connect the outside plant facilities to
the premise cabling. It is beyond the scope of this paper to address this.
Cabling Installation Requirements
Just as import as choosing compliant connecting hardware and following the
installation design guidelines of these standards is installation practices.
Even the best cable and components improperly installed will not work, or at
least not to its full potential.
Some of the most important installation requirements for UTP in order of
importance include:
- Cable pair twist shall be maintained to within 13 mm (0.5 in) from the
point of termination. UTP gets a great deal of its performance attributes
from the twist of the paired cables. It does not take much untwist to cause
a measurable drop in performance. This is by far the most important factor
for installation factors. Treat shall as shall, must, do not deviate or
whatever else you want to call it but do meet this recommendation.
- While it may be obvious all cables shall be terminated with connecting
hardware of the same category or higher. Terminating Category 5e cable on
Cat 3 connectors will definitely hurt cabling performance. The same goes for
the use of patch cords.
- The minimum bend radius for horizontal UTP cable shall be four times the
cable diameter, or in other words avoid sharp bends. To emphasize the
importance of untwist the primary reason for this recommendation is that
sharper bends tend to straighten out the twist in the pairs! There is no
minimum bend radius for patch cables at this time.
- Watch how hard you pull the cable. The maximum pulling tension of 4 pair
24 AWG UTP cable shall be 110 N (25lbf). Can you guess why this
recommendation exists? That’s right, be pulling too hard you untwist the
pairs effecting performance!!
- Use common sense when laying out the cable. For example do not run the
horizontal cable right over fluorescent lights and wonder why you are
picking up stray noise!
For fiber the following applies in order of priority:
- Do not untwist …. Just seeing if you were paying attention. Fiber is the
opposite. Twist it and it will break. The bend radius is the most important
factor. Bend it too sharp and may not only degrade the signal but break and
lose all the signal. The bend radius for 2 and 4 horizontal optical fiber
cable shall not be less than 25 mm (1 in) under no load conditions. For
backbone cable the bend radius shall not be less than 10 times the cable
diameter unless otherwise recommended by the manufacture.
- Proper connector termination is absolutely a must. The quality of the
polish greatly determines the performance of the cabling system. There are
many field terminable connectors that include a pre-polished stub that all
you do is butt up the fiber cable to and terminate. It is not quite that
easy but it is sure beats having to field polish the termination in
generally less than ideal conditions.
- And again use common sense keeping in mind the need to avoid sharp bends
in the cable.
Testing
OK so you have bought all the right stuff and followed all the design
recommendations and installed it perfectly, how do you test it? The exact test
criteria is set out in great detail in the standards for both copper and fiber
cabling and we will not go in great detail here on that. However you don’t need
to worry about these as testers exists that are certified to meet the standards
and you just need to learn how to use them. They will tell you whether they meet
the category of performance you are testing for, and depending on their features
can help you isolate the problem.
There are two test used in the field to test a copper system, Channel test
(Figure 8) and a Permanent Link test (Figure 9). The Channel test includes all
components of the horizontal cabling system including the patch cords. This is
the better test regarding actual performance. The Link test exists as there are
many times cabling systems is installed before any office equipment is moved in
or telecommunication room equipment is installed. This provides a test for the
installer or contractor to verify the performance of the installation lacking
the equipment patch cords.

Figure 9

Figure 10
For fiber the test are just as straight forward providing you have a
certified tester.
What are Categories for UTP cabling systems?
So what is Category 3, 5, 5e and 6? And why should I care? The recognized
categories of twisted pair cable by EIA/TIA 568 are:
- Category 3: This designation applies to 100 ohm cable whose transmission
characteristics are specified up to 16 MHz.
- Category 5e: This designation applies to 100 ohm cable whose
transmission characteristics are specified up to 100 MHz
- Category 6: This designation applies to 100 ohm cable whose transmission
characteristics are specified up to 250 MHz
Cable, Patch Cords, and Connecting Hardware are all rated one of these
categories. It is critical to note that rating of a cabling system is determined
by its lowest rated component! If you have Cat 6 cable and connecting hardware
everywhere but use a Cat 3 patch cord, you have a Cat 3 system. Don’t do this.
For practical application Category 3 support 10BaseT Ethernet networks.
Category 5e supports 10BaseT, 100BaseT and 1000BaseT (yes it really supports 1
gigabit LAN’s over UTP). Category 6 supports everything Cat5e and will support
10GBaseT or 10Gigabit LAN’s
Industrial Considerations
So what changes for the industrial environment related to the SCSI? Actually very
little. All the same standards apply including installation requirements and
test requirements. And if you mount everything inside NEMA rated enclosures then
nothing changes at all. However if you want to plug into the network from
outside the enclosure there is a new connector style available called and
Industrial RJ45. The specifications are being developed by EIA/TIA and ODV and
are nearly complete.
This new connector interface, see Figure 11, contains at its core the 8 pin
modular plug and connector specified in EIA/TIA 568. It is however surrounded
with other mechanical connections to seal it against the environment with
ratings such as IP67.

Figure 11
For an explanation of the IP rating system see Figure 12 below.

Conclusions
- Structured Cabling in using an organized approach to the design and
installation of the cabling based on EIA/TIA 568 specifications.
- Critical issues to keep in mind include
- Use EIA/TIA compliant cables, patch cords and connecting hardware
- Do not exceed the 90 m horizontal cable length limits
- Use the correct performance Category components to match the
application. B&B recommends Cat 5e for UTP as it will support up to 1000
BaseT LAN’s.
- Do not untwist UTP, do not over bend Fiber
- When using fiber look into the pre-terminated stub connectors on the
market.
- To know if you did it right there are testers designed just for this
application for both copper cabling and fiber cabling.
- If you want more details buy the EIA/TIA specifications and read
them yourself.
- There is an industrial variation of the modular connector interface with
a NEMA IP67 rating for tough industrial environments. The standard is still
pending so interoperability may be an issue if you mix and match components
from multiple vendors
|