|
When using or installing any RS-232 port
powered device, it is important to keep a few things in mind. The two
main items are the Power Available from the RS-232 port and the Power
Dissipated by the RS-422 or RS-485 system.
Power Dissipation
The power dissipated when using a port powered converter
is consumed by:
 | The cable on the RS-232 side of the converter.
|
 | Termination resistors used on the RS-422 or RS-485 transmission
line.
|
 | The RS-422 or RS-485 cable.
|
 | The port powered converter. |
It is assumed in this discussion that the RS-232 cable
is short, 1.8 meters (6 feet), so that the RS-232 cable power is
insignificant. The power dissipated by our typical port powered
converter is 50 mW. Figure 1 shows the power dissipated by 2000 ft. (600
m) and 4000 ft. (1200 m) of transmission line (unterminated). For the
data shown in Figure 1, the RS-422 line driver was not power limited by
an RS-232 port. This table clearly shows that the line power increases
as the data rate increases. The transmission line used in this example
is a high quality polyethylene cable recommended for RS-422 & RS-485
applications. The port powered converter is operating at the highest
power consumption when it is transmitting data to the RS-422 or RS-485
line. All available power that is not used by the internal converter
circuit is used to drive power to the transmission line.
The power dissipated by the termination resistors is
significant (75 mW for a very short transmission line). Under certain
conditions it is not necessary to terminate the RS-422 or RS-485
transmission line. If the system is operating at low speed or short
cable lengths, it does not need to be terminated. Low speed is
considered to be signaling rates below 200 kbits/sec. or when the cable
delay (the time required for an electrical signal to transverse the
cable) is substantially shorter than the bit width or when the signal
rise time is more than four times the one way propagation delay of the
cable (i.e. not a transmission line). As a general rule, if the signal
rise time is greater than four times the propagation delay of the cable,
the cable is no longer considered a transmission line. For most cables,
which are 4000 ft. (1200 m) or shorter and baud rates at 19.2k baud or
lower, termination is not required.
The RS-232 Port As A Power Supply
An RS-232 port can supply only limited power to another
device. The number of output lines, the type of interface driver IC, and
the state of the output lines are important considerations.
The types of driver ICs used in serial ports can be
divided into three general categories:
 | Drivers which require plus (+) and minus (-) voltage power
supplies such as the 1488 series of interface integrated circuits.
(Most desktop and tower PCs use this type of driver.)
|
 | Low power drivers which require one +5 volt power supply. This
type of driver has an internal charge pump for voltage conversion.
(Many industrial microprocessor controls use this type of driver.)
|
 | Low voltage (3.3 v) and low power drivers which meet the EIA-562
Standard. (Used on notebooks and laptops.) |
Table 1 is a comparison of several types of driver ICs.
For driver ICs, their ability to deliver power is greater if the output
of the driver is in the positive voltage state.
What Type of Driver Do i Have On My Port?
To determine the type of driver used on a
serial port without looking at the ICs, put a 3K ohm load on the driver
output line to signal ground and measure the voltage. If possible
measure the voltage under both (+) and (-) voltage conditions. These
voltage measurements should give values as shown below.
|
1488 Driver |
+/- 9 volts |
< Vout |
<+/- 11 volts |
|
Charge Pump Driver |
+/- 7.5 volts |
< Vout |
<+/- 8 volts |
|
EIA-562 Driver |
+/- 3.7 volts |
< Vout |
<+/- 5 volts |
Loop Back Connections
Many port powered converters will have
loop back connections, such as RTS connected to CTS. These loop back
connections each dissipate about 8.3 mW per input line. The only reason
to make these connections is that some software requires these
connections. If you have control over the software, change the software
so that the loop back conditions are not required. Also, don't complete
the loop back connections in the cables you are using. (See Figure 2.)

Figure 2. PC Serial Port Used With Port Powered Converter
Summary of Tips
 | Connect all port driver lines to the converter.
|
 | Keep all unused port driver lines in positive voltage state.
|
 | Determine if the port can drive the converter (what type of
driver).
|
 | Don't terminate the transmission line, if not necessary.
|
 | Don't make loop back connections, if not necessary. |
For more information on serial ports, we recommend
Serial Port Complete and
C Programmer's Guide to Serial Communication.
RS232, RS422, RS485
|